Industrial Ventilation Systems
Air change, fresh air and exhaust balance in production areas; system design based on airflow calculation.
Filtration to hygiene class, humidity and temperature control.
In food production, ventilation is not a comfort issue but part of the production conditions. Temperature, humidity and particle load in the room directly affect a product's shelf life, its microbiological safety and often its appearance. That is why in food facilities ventilation is handled as part of the hygiene plan.
The most decisive design decision in a food facility is which area is kept at higher pressure than its neighbour. Areas where the product is exposed — filling, slicing, pre-packaging — are kept at positive pressure relative to their surroundings; air always flows from clean to less clean. Raw material intake, waste and washing areas are kept negative.
Without this cascade, much of the investment in filters is wasted: every time a door opens, corridor air floods into the production area.
Humidity in food facilities is a two-sided problem. High humidity leads to condensation on surfaces, dripping from ceilings and a risk of mould. Low humidity means drying and weight loss in some products.
In areas cleaned with water, the humidity load is sudden and high. Ventilation must be sized not only for production hours but also for the cleaning shift; otherwise the room is still damp when production starts in the morning.
Supply air passes through staged filters. In areas where the product is exposed, HEPA can be used as the final stage. Cleanability is decisive in the choice of grilles, ducts and diffusers; a profile that collects dust is a source of problems in a hygienic area.
Hygienic air handling units are built for this field: the interior has no corners, surfaces are cleanable and the condensate pan is sloped so that no standing water remains.
Condensation is unavoidable when moving from a cold area to a warm one. Air curtains and buffer zones at connecting doors reduce both energy loss and condensation. If this detail is not considered at the design stage, it is hard to fix later.
Cooking, frying and fermentation areas carry a high odour load. Their exhaust is kept separate and discharged at a point away from the fresh air intake. Air from waste and washing areas is planned so that it never returns to the production area under any condition.
In food facilities it must be documented that ventilation works. At commissioning, pressure differences, airflows and filter condition are measured and reported; these measurements are repeated during periodic maintenance. These records are exactly the documents requested in audits.
The most common situation in food facilities is that ventilation exists but no pressure cascade was ever set up. In that case the solution is usually not to rebuild the system: exhaust and fresh air airflows are measured, the differences between areas are rebalanced in the intended direction, and door and transition details are corrected. With a relatively small intervention, hygiene conditions improve significantly.
The second common gap is that the cleaning shift was not taken into account. The humidity load during wet cleaning is higher than during production and must be assessed separately.
In food facilities, ventilation investment often comes up after an audit finding. Acting early both lowers the cost and makes it possible to work without stopping production.
Air change, fresh air and exhaust balance in production areas; system design based on airflow calculation.
Heating, cooling, humidification and filtration with air handling units; climate control matched to process conditions.
HEPA filtration, pressure cascades and clean room classification for food, pharmaceutical and healthcare facilities.
Pulse-jet filters, cyclones and central dust collection lines; source capture and filter selection.
Capturing welding fume, oil mist and process fume at source; cartridge filters and central systems.
Canopy hoods, grease filters, exhaust and fresh air balance for large-scale catering and industrial kitchens.
One call is enough to book a site survey. We take the measurements and pin down the solution and cost.
Ertuğrul Mh. Ertuğrul Sk. No:24/A, Nilüfer / Bursa
We will get back to you.